重置
重置
| Product Name |
Eaton Moeller® series EASY Control relay
|
| Catalog Number |
197215
|
| Product Length/Depth |
58 mm
|
| Product Height |
90 mm
|
| Product Width |
72 mm
|
| Product Weight |
0.25 kg
|
| Compliances |
Eaton supports the product until its end of life
|
| Certifications |
UL File No.: E205091
CE UL hazardous location group C (ethylene) UL hazardous location class I UL hazardous location group D (propane) UL hazardous location group A (acetylene) UL hazardous location group B (hydrogen) UL hazardous location division 2 cULus Ordinary Location DNV TAA00002HT cULus Hazard Location UL File No.: E523283 EN 61131-2 IEC 61131-2 EN IEC 61000-6-3 IEC 61000-6-3 EN IEC 61010-2-201 IEC 61010-2-201 UL 61010-1 UL 61010-2-201 CSA C22.2 No. 61010-1 CSA C22.2 No. 61010-2-201 UL 121201 CSA C22.2 No. 213 |
| Catalog Notes |
Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible
|
| Used with |
easyE4
|
| Type |
easyE4 base device
|
| Features |
Networkable (Ethernet)
Expandable Display indication of 6 lines x 16 characters |
| Air discharge |
8 kV
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Cable type |
Ethernet: CAT5
|
| Fitted with: |
Relay output
Timer Keypad Display Real time clock |
| Pollution degree |
2
|
| Accuracy |
± 1 %, Repetition accuracy of timing relays (of values)
± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year) |
| Burst impulse |
2 kV, I/O port
2 kV, Power supply port 1 kV, communication port According to IEC/EN 61131-2 |
| Utilization category |
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC |
| Rated impulse withstand voltage (Uimp) |
Relay outputs: 6 kV (contact-coil)
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Category (EN 954-1) |
None
|
| Explosion safety category for dust |
None
|
| Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201 |
| Indication |
LCD-display used as status indication of digital I/Os
|
| Explosion safety category for gas |
None
|
| Mounting method |
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Rail mounting possible Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Wall mounting/direct mounting Front build in possible |
| Screwdriver size |
3.5 x 0.6 mm, Terminal screw
|
| Voltage type |
AC/DC
|
| Mounting position |
Horizontal
Vertical |
| Output |
4 Relay Outputs
min. recommended load: 12 V AC/DC > 500 mA |
| Contact discharge |
6 kV
|
| Base type |
Yes
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Display temperature - max |
55 °C
|
| Display temperature - min |
0 °C
|
| Equipment heat dissipation, current-dependent Pvid |
1 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Number of HW-interfaces (industrial ethernet) |
1
|
| Number of HW-interfaces (other) |
0
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of HW-interfaces (wireless) |
0
|
| Overvoltage category |
Power supply + Inputs + Extension interface: III
Relay outputs: III |
| Duty factor |
100 %
|
| Software |
EASYSOFT-SWLIC/easySoft
|
| Surge rating |
1 kV, Line-to-Line, Power supply port
2 kV, Line-to-Earth, Power supply port 1 kV, Line-to-Line, Input port 2 kV, Line-to-Earth, Input port 1 kV, Line-to-Earth, communication port According to IEC/EN 61131-2 |
| Cable length |
Digital inputs (I1 - I6, AC): ≤ 40 m (unshielded)
Digital inputs (I7 - I8, AC): ≤ 100 m (unshielded) |
| Electromagnetic fields |
10 V/m at 0.08 - 1.0 GHz (according to IEC/EN 61131-2)
3 V/m at 1.0 - 6 GHz (according to IEC/EN 61131-2) |
| Display type |
Monochrome
|
| Protection against polarity reversal |
Yes
|
| Number of inputs (analog) |
0
|
| Connection type |
Screw terminal
Ethernet: RJ45 plug, 8-pole |
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61131-2)
|
| Radio interference class |
Class B (EN 61000-6-3)
|
| Number of outputs (digital) |
4
|
| Data transfer rate |
10/100 MBit/s
|
| Relative humidity |
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
|
| Degree of protection |
IP20
|
| Safe isolation |
Relay outputs: 300 V AC, Between two contacts
Relay outputs: 300 V AC, Between coil and contact |
| Delay time |
Digital inputs (100 - 240 V DC): 20 ms, from 0 to 1, Debounce ON
Digital inputs (100 - 240 V DC): 0.03 ms typ., from 0 to 1, Debounce OFF Digital inputs (100 - 240 V DC): 20 ms, from 1 to 0, Debounce ON Digital inputs (100 - 240 V DC): 0.03 ms typ., from 1 to 0, Debounce OFF Digital inputs (100 - 240 V AC 50 Hz): 45 ms, from 0 to 1, Debounce ON Digital inputs (100 - 240 V AC 50 Hz): 45 ms, from 1 to 0, Debounce ON Digital inputs (100 - 240 V AC 60 Hz): 38 ms, from 0 to 1, Debounce ON Digital inputs (100 - 240 V AC 60 Hz): 21 ms typ., from 0 to 1, Debounce OFF Digital inputs (100 - 240 V AC 60 Hz): 38 ms, from 1 to 0, Debounce ON Digital inputs (100 - 240 V AC 60 Hz): 21 ms typ., from 1 to 0, Debounce OFF Digital inputs (100 - 240 V AC 50 Hz): 25 ms typ., from 1 to 0, Debounce OFF Digital inputs (100 - 240 V AC 50 Hz): 25 ms typ., from 0 to 1, Debounce OFF |
| Protocol |
Modbus TCP
|
| Residual ripple |
Power supply: ≤ 5 %
|
| Supply frequency |
50/60 Hz (± 5%)
|
| Insulation resistance |
According to EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-203
|
| Vibration resistance |
8.4 - 150 Hz, 1 g constant acceleration
5 - 8.4 Hz, 3.5 mm constant amplitude According to IEC/EN 61131-2 |
| Input current |
2 x 4 mA (I7 - I8, at 115 VAC, 60 Hz, at signal 1)
6 x 0.25 mA (I1 - I6, at 115V AC, 60 Hz, at signal 1) 2 x 6 mA (I7 - I8, at 230 VAC, 50 Hz, at signal 1) 6 x 0.5 mA (I1 - I6, at 230 VAC, 50 Hz, at signal 1) |
| Shock resistance |
15 g, Mechanical, acc. to IEC/EN61131-2, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Input frequency |
50/60 Hz (Digital inputs at AC)
|
| Input voltage |
Condition 0: 0 - 40 V AC/DC (Digital inputs)
Condition 1: 79 - 264 V AC/DC (Digital inputs) |
| Rated breaking capacity |
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)
200000 Operations at DC-13, L/R ≦ 150 ms, 24 V DC, 1 A (500 Ops./h) |
| Lifespan, electrical |
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) |
| Lifespan, mechanical |
10,000,000 Operations
|
| Making/breaking capacity |
3600/360 VA (AC, at B 300)
28/28 VA (DC, at R 300) |
| Parallel switching |
Not permitted
|
| Potential isolation |
Power supply + Inputs + Extension interface against Outputs: yes
POW+Inputs+Extension interface vs. Ethernet+Functional Earth: yes Outputs against Ethernet + Functional Earth: yes Outputs against each other: yes |
| Number of inputs (digital) |
8
|
| Power loss |
10 VA
|
| Voltage dips |
10 ms at 100 V DC
20 ms at 100 V AC |
| Uninterrupted current |
5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA)
8 A AC, at 240 V AC (UL/CSA) 8 A DC, at 24 V DC (UL/CSA) 1 A DC, at R 300 (UL/CSA) 10 A AC, at 240 V AC (UL/CSA) |
| Number of interfaces (PROFINET) |
0
|
| Number of outputs (analog) |
0
|
| Static heat dissipation, non-current-dependent Pvs |
4 W
|
| Supply voltage at AC, 50 Hz - max |
264 VAC
|
| Supply voltage at AC, 50 Hz - min |
85 VAC
|
| Supply voltage at AC, 60 Hz - max |
264 VAC
|
| Supply voltage at AC, 60 Hz - min |
85 VAC
|
| Supply voltage at DC - max |
264 VDC
|
| Supply voltage at DC - min |
85 VDC
|
| Switching current |
8 A
|
| Product category |
Control relays easyE4
|
| Protection |
B16 circuit breaker or 8 A (T) fuse, Protection of an Output relay
|
| Power consumption |
4 W
|
| Rated operational voltage |
Power supply: 100 - 240 V AC (-15 %/+ 10 %)
Power supply: 100 - 240 V DC (-15 %/+ 10 %) (IEC) Power supply: 100 - 110 V DC (-15 %/+ 10 %) (cULus) Relay outputs: max. 300 V AC/DC Inputs: shall be identical to the power supply voltage |
| Short-circuit protection |
≥ 1A (T), Fuse, Power supply
|
| Switching frequency |
10 Hz, Relay outputs
2 Hz, Resistive load/lamp load, Relay outputs 0.5 Hz, Inductive load, Relay outputs |
| Terminal capacity |
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm², flexible with ferrule 0.2 - 2.5 mm², flexible without ferrule |
| Tightening torque |
0.6 Nm, Screw terminals
|