Reset
Eaton Moeller® series EASY Control relays easyE4 with display (expandable, Ethernet), 12/24 V DC, 24 V AC, Inputs Digital: 8, of which can be used as analog: 4, push-in terminal
| Product Name |
Eaton Moeller® series EASY Control relay
|
| Catalog Number |
197504
|
| Product Length/Depth |
58 mm
|
| Product Height |
90 mm
|
| Product Width |
72 mm
|
| Product Weight |
0.25 kg
|
| Compliances |
Eaton supports the product until its end of life
|
| Certifications |
EN 55011
IEC/EN 61000-4-2 EN 55022 IEC 60068-2-6 IEC/EN 61000-4 IEC 60068-2-27 UL Listed UL Category Control No.: NRAQ, NRAQ7 IEC/EN 61131-2 IEC 60068-2-30 EN 61010 IEC/EN 61000-6-3 IEC/EN 61000-6-2 EN 50178 UL File No.: E205091 DNV GL CE UL hazardous location group B (hydrogen) UL hazardous location group C (ethylene) UL hazardous location class I UL hazardous location group A (acetylene) UL hazardous location division 2 UL hazardous location group D (propane) |
| Catalog Notes |
Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible
|
| Used with |
easyE4
|
| Type |
easyE4 base device
|
| Features |
Expandable
Networkable (Ethernet) |
| Air discharge |
8 kV
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Cable type |
CAT5
|
| Fitted with: |
Display
Relay output Timer Keypad Real time clock |
| Pollution degree |
2
|
| Accuracy |
± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year)
± 1 %, Repetition accuracy of timing relays (of values) ± 2 %, (I7, I8) ± 0.12 V, of actual value, within a single device (Analog Inputs) ± 3 %, of actual value, two easy devices (Analog Inputs) |
| Burst impulse |
2 kV, Signal cable
2 kV, Supply cable According to IEC/EN 61000-4-4 |
| Utilization category |
B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC
R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC |
| Rated impulse withstand voltage (Uimp) |
6 kV (contact-coil)
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Explosion safety category for dust |
None
|
| Environmental conditions |
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures |
| Indication |
LCD-display used as status indication of Digital inputs 12 V DC
LCD-display used as status indication of Digital inputs 24 V DC |
| Input |
Voltage (DC)
|
| Explosion safety category for gas |
None
|
| Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Screw fixing using fixing brackets ZB4-101-GF1 (accessories) Front build in possible Rail mounting possible Wall mounting/direct mounting |
| Voltage type |
AC/DC
|
| Mounting position |
Horizontal
Vertical |
| Output |
Voltage
Relay outputs in groups of 1 > 500 mA (Relay outputs, Recommended for load: 12 V AC/DC) Current 4 Relay Outputs |
| Contact discharge |
6 kV
|
| Base type |
No
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
8 A
|
| Equipment heat dissipation, current-dependent Pvid |
4 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Number of HW-interfaces (industrial ethernet) |
1
|
| Number of HW-interfaces (other) |
0
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of HW-interfaces (wireless) |
0
|
| Overvoltage category |
III
|
| Software |
EASYSOFT-SWLIC/easySoft
|
| Surge rating |
1 kV, Supply cables, symmetrical, power pulses (Surge), EMC
2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC According to IEC/EN 61000-4-5 Level 4 |
| Cable length |
30 m, screened, Analog inputs
40 m (max. per input), Digital inputs 24 V DC 100 m, unscreened, Digital inputs 12 V DC 100 m, unscreened, Digital inputs 24 V AC |
| Conversions |
Each CPU cycle, Analog inputs
|
| Electromagnetic fields |
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Display type |
Monochrome
|
| Protection against polarity reversal |
Yes
|
| Number of inputs (analog) |
4
|
| Connection type |
Ethernet: RJ45 plug, 8-pole
Push in terminals |
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 61000-6-3)
|
| Number of outputs (digital) |
4
|
| Data transfer rate |
10/100 MBit/s
|
| Relative humidity |
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
|
| Degree of protection |
IP20
|
| Safe isolation |
300 V AC, Between coil and contact, According to EN 50178
300 V AC, Between two contacts, According to EN 50178 |
| Delay time |
20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON
20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON 20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON 0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF 0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF 0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF 0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF 20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON |
| Protocol |
MODBUS
TCP/IP |
| Residual ripple |
5 % (transistor outputs)
≤ 5 % |
| Rapid counter inputs |
1:1 (Pulse pause ratio)
10 kHz, Counter frequency ≤ 20 m (cable length, screened) -2147483648 - 2147483647 (value range) Square (pulse shape) Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) |
| Supply frequency |
50/60 Hz (± 5%)
|
| Insulation resistance |
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
|
| Incremental counter |
Pulse shape: Square
Signal offset: 90° Counter frequency: ≤ 5 kHz Number of counter inputs: 2 (I1 + I2, I3 + I4) Pulse pause ratio: 1:1 Value range: -2147483648 to +2147483647 |
| Vibration resistance |
10 - 57 Hz, 0.15 mm constant amplitude
According to IEC/EN 60068-2-6 57 - 150 Hz, 2 g constant acceleration |
| Incremental encoder |
Cable length: ≤ 20 m (screened)
|
| Input impedance |
13.3 kΩ
|
| Input current |
200 mA
|
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Frequency counter |
Pulse shape: Square (digital inputs 24 V DC)
Cable length: ≤ 20 m (screened, Digital inputs 24 V DC) Counter frequency: 5 kHz (Digital inputs 24 V DC) Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) Pulse pause ratio: 1:1 (Digital inputs 24 V DC) |
| Input frequency |
50/60 Hz (Digital inputs, at 115/230 V AC)
50/60 Hz (Digital inputs, at 24 V DC) |
| Input voltage |
Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC)
Signal 0: ≤ 5 V DC (I1 - I8, Digital inputs, 24 V DC) |
| Rated breaking capacity |
200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h)
300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h) |
| Lifespan, electrical |
25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated)
25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) 25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC) |
| Signal range |
0 - 10 V DC, Analog inputs
|
| Lifespan, mechanical |
1,000,000 Operations
|
| Making/breaking capacity |
28/28 VA (DC, at R 300)
3600/360 VA (AC, at B 300) |
| Potential isolation |
Basic isolation: 600 V AC (Relay outputs)
Between Analog inputs and Digital inputs: no Between Relay outputs: yes |
| Number of inputs (digital) |
4
8 |
| Voltage dips |
≤ 1 ms from rated voltage (12 V DC)
10 ms |
| Uninterrupted current |
1 A DC, at R 300 (UL/CSA)
10 A AC, at 240 V AC (UL/CSA) 8 A DC, at 24 V DC (UL/CSA) 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) |
| Number of interfaces (PROFINET) |
0
|
| Number of outputs (analog) |
0
|
| Rated insulation voltage (Ui) |
240 V
|
| Static heat dissipation, non-current-dependent Pvs |
3 W
|
| Supply voltage at AC, 50 Hz - max |
26.4 VAC
|
| Supply voltage at AC, 50 Hz - min |
20.4 VAC
|
| Supply voltage at AC, 60 Hz - max |
26.4 VAC
|
| Supply voltage at AC, 60 Hz - min |
20.4 VAC
|
| Supply voltage at DC - max |
28.8 VDC
|
| Supply voltage at DC - min |
10.2 VDC
|
| Switching current |
8 A
|
| Product category |
Control relays easyE4
|
| Protection |
Miniature circuit-breaker B16 or slow-blow 8 A fuse, Protection of an output relay
|
| Resolution |
|
| Power consumption |
3 W
|
| Rated operational voltage |
Max. 300 V AC
Max. 300 V DC 85 - 264 V AC 100/110/115/120/230/240 AC (-15 %/+10 %) |
| Short-circuit protection |
≥ 1A (T), Fuse, Power supply
|
| Switching frequency |
0.5 Hz, Inductive load, Relay outputs
10 Hz, Relay outputs 2 Hz, Resistive load/lamp load, Relay outputs |
| Terminal capacity |
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule |