Eaton Modular PLC XC204, Micro PLC, programmable CODESYS 3, USB, Ethernet, CAN, RS485, XN300 IO expandable
Product Name |
Eaton XC200 modular PLC
|
Catalog Number |
199974
|
Product Length/Depth |
104.2 mm
|
Product Height |
29.3 mm
|
Product Width |
80.3 mm
|
Product Weight |
0.11 kg
|
Certifications |
UL listed
EN 61131 EAC UL File No.: E205091 CE cULus Listed |
Type |
Modular PLC XC204
|
Air discharge |
8 kV/6 kV, Air/contact discharge, ESD
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
XSOFT-CODESYS 3
|
Pollution degree |
2
|
Burst impulse |
1 kV, Signal cable
2 kV, Supply cable |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
Air pressure |
795 - 1080 hPa (operation)
|
Explosion safety category for dust |
None
|
Environmental conditions |
Condensation: prevent with appropriate measures
|
Explosion safety category for gas |
None
|
Mounting method |
Rail mounting possible
|
Voltage type |
DC
|
Mounting position |
Vertical (on horizontal top-hat rail)
|
Memory capacity |
512,000 kByte
|
Number of channels |
0
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
-20 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-25 °C
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
2
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (USB) |
1
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
0
|
Overvoltage category |
II
|
Surge rating |
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
1 kV, Signal cable, unbalanced, EMC |
Emitted interference |
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency)
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency) |
Terminal capacity (AWG) |
24 - 16
|
Electromagnetic fields |
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
Load current |
Max. 6 A per 1.5 mm² (cross-sectional area)
|
Number of inputs (analog) |
0
|
Connection type |
Push-in spring-cage terminal, Connection design in TOP direction
|
Radiated RFI |
10 V
|
Memory type |
RAM
|
Number of outputs (digital) |
0
|
CPU module type |
CORTEX A7@800MHz
|
Relative humidity |
< 95 % (non-condensing)
|
Degree of protection |
IP20
|
Number of relay outputs |
0
|
Protocol |
CAN
EtherNet/IP MODBUS Other bus systems TCP/IP |
Rated operational current (Ie) |
1.4 A (supply input)
|
Functions |
Additional program memory possible
|
Gauge pin |
A1 (according to IEC/EN 60947-1)
|
Vibration resistance |
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Number of time switches - max |
1000
|
Processing time |
1.25 microsecond
|
Static heat dissipation, non-current-dependent Pvs |
6.3 W
|
Stripping length (main cable) |
10 mm
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
30 VDC
|
Supply voltage at DC - min |
19.2 VDC
|
Heat dissipation details |
The max. heat dissipation is specified as the maximum power produced inside the device's housing.
|
Insulating material group |
I
|
Terminal capacity (flexible) |
0.2 - 1.5 mm², H 07V-K
|
Interfaces |
ETH
CAN RS485 XN300 |
System accessory |
Yes
|
Model |
Modular
|
Number of inputs (digital) |
0
|
Voltage dips |
20 ms
10 ms |
Rated operational voltage |
24 V
160 V (terminations) |
Terminal capacity |
0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
|
Terminal capacity (flexible with ferrule) |
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25 - 1.5 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
Terminal capacity (solid) |
0.2 - 1.5 mm², H07V-U
|