Eaton 5P UPS, 1150VA, 770W, AU 10A input, Outputs: (2) AU 10A; (3) IEC C13, 230V, Tower
Product Name |
Eaton 5P UPS
|
Catalog Number |
5P1150AU
|
Product Length/Depth |
150 mm
|
Product Height |
230 mm
|
Product Width |
345 mm
|
Product Weight |
11.1 kg
|
Compliances |
C-Tick Compliant
CB |
Certifications |
IEC/EN 62040-1
EN 62040-3 IEC/EN 62040-2 |
Special features |
|
Topology |
Line-interactive
|
Form factor |
Tower
|
Construction type |
Free standing model
|
Color |
Black/silver
|
VA rating |
1150 VA
|
Wattage |
770 W
|
Rack mounting kit |
No
|
Package contents |
|
Auto shutdown function |
Yes
|
Input connection |
Fixed connection
|
Input nominal voltage |
230V default (200/208/220/230/240V)
|
Input frequency range |
47-70 Hz (50 Hz system), 56.5-70 Hz (60 Hz system), 40-70 Hz in low-sensitivity mode
|
Receptacle |
(2) AU; (3) IEC C13
|
Output waveform |
Sine wave
|
Voltage |
230V
|
Output nominal voltage |
230V default (200/208/220/230/240V)
|
Runtime graph |
View runtime graph
|
Battery management |
ABM or constant voltage charging method (user selectable), automatic battery test, deep discharge protection
|
Battery replacement |
User replaceable
|
Battery type |
Sealed, lead-acid
|
Extended battery capability |
None; See Eaton 5PX UPS for extended runtimes options
|
Communication |
1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously), 1 mini-terminal block for remote ON/OFF and Remote Power Off
|
Expansion slots |
One slot for optional communication card
|
Ethernet interface |
No
|
Includes network card |
No
|
Software compatibility |
Eaton Intelligent Power Manager, Eaton Intelligent Power Protector
|
User interface |
Multilingual graphical LCD display
|
Type of interface |
Other
|
Potential free switch contact |
Yes
|
Altitude |
2000 m
|
Noise level |
<40 dB at 1 meter
|
Relative humidity |
0-90% non-condensing
|
Temperature range |
0° to 35°C (32° to 95°F)
|
Efficiency at max. load |
Up to 98%
|
Input voltage range |
160-294 V (adjustable to 150 V-294 V)
|
Output frequency |
50/60 Hz ±0.1 % (autosensing)
|
Output voltage range |
230 V (+6%/-10%)
|
Phase (input) |
Single-phase
|
Phase (output) |
Single-phase
|
Runtime at full load |
4 min
|