Eaton S711 Soft starter, 75 A, 200 - 575 V AC, Us= 24 V DC, with control unit, Frame size 2, IP20
| Product Name |
Eaton S711 soft starter
|
| Catalog Number |
EP-401538
|
| Product Length/Depth |
281 mm
|
| Product Height |
190 mm
|
| Product Width |
128 mm
|
| Product Weight |
5.1 kg
|
| Certifications |
CE
RCM IEC/EN 60947-4-2 CUL UL UL Category Control No.: NMFT UL Category Control No.: NMFT7 UL File No.: E251034 UL 60947-4-2 |
| Type |
Soft starter for three-phase loads, with control unit and pump algorithm, DC Brake, Soft Brake, Jog, Bluetooth
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Display
Motor overload protection Internal bypass |
| Pollution degree |
3
|
| Class |
Adjustable (5,10,15,20,30)
|
| Climatic proofing |
5 to 95% Relative Humidity
|
| Connection to SmartWire-DT |
No
|
| Rated impulse withstand voltage (Uimp) |
6000 V
|
| Frame size |
FS2
|
| Altitude |
Max 4000 m (Above 1000 m for detailed derating use S711 Select Software)
|
| Number of inputs |
5 (2 fixed, 2 programmable, 1 thermistor)
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Assigned motor power at 200/208 V, 60 Hz, 3-phase |
20 HP
|
| Assigned motor power at 220/230 V, 60 Hz, 3-phase |
25 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
50 HP
|
| Assigned motor power in-delta at 220/230 V, 60 Hz |
40 HP
|
| Assigned motor power in-delta at 460/480 V, 60 Hz |
75 HP
|
| Assigned motor power in-delta at 575/600 V, 60 Hz |
100 HP
|
| Equipment heat dissipation, current-dependent Pvid |
337.5 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Mains voltage - max |
632.5 V
|
| Mains voltage - min |
170 V
|
| Output voltage |
250 V AC (relay outputs)
|
| Number of outputs |
3 Relay Outputs (1 fixed, 2 programmable)
|
| Screwdriver size |
1 x 7 mm or T20, Terminal screw, Main cables
0.6 x 3.5 mm or PH0, Terminal screws, Control circuit cables |
| Voltage type |
DC
|
| Rated operational voltage (Ue) - min |
200 V
|
| Rated operational voltage (Ue) at AC - max |
575 V
|
| Rated power three-phase motor, inline, at 230 V |
22 kW
|
| Rated power three-phase motor, inline, at 400 V |
37 kW
|
| Rated power three-phase motor, inside delta, at 230 V |
30 kW
|
| Rated power three-phase motor, inside delta, at 400 V |
55 kW
|
| Static heat dissipation, non-current-dependent Pvs |
50 W
|
| Voltage rating - max |
575 V
|
| Application |
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact
|
| Assigned motor power at 575 V_ 60 Hz_ 3-phase |
60 HP
|
| Mounting position |
As required
|
| Drop-out voltage |
0 - 16 V, DC operated
|
| Degree of protection |
IP20
NEMA 1 |
| Current consumption |
2800 mA, Control circuit, Digital inputs
|
| Functions |
Single direction
Torque control DC-Brake Soft-Brake Forward & reverse jog |
| Delay time |
0 - 180 s, Soft start function, Ramp times; 0 - 240 s, Soft stop function, Stop times
|
| Overload cycle |
AC-53b: 3.5-20:340
|
| Pick-up voltage |
19.2 - 28.8 V DC
|
| Radio interference class |
Class A (IEC 60947-4-2)
|
| Fault memory |
1000 Faults
|
| Interfaces |
Modbus RTU (built-in)
Bluetooth (built-in) |
| Kickstart |
600% (Kickstart current)
Max. 2000 ms (Kickstart Duration) |
| Rated control voltage (Uc) |
24 V DC (-20 %/+20 %)
|
| Supply frequency |
50/60 Hz, fLN, Main circuit
|
| Terminal capacity (stranded) |
1 x (6 - 70) mm², Main cables
1x (1 - 2.5) mm², Control circuit cables |
| Rated control supply voltage (Us) at DC - max |
24 VDC
|
| Rated control supply voltage (Us) at DC - min |
24 VDC
|
| Rated insulation voltage (Ui) |
600 V
|
| Rated operational current (Ie) at AC-11 |
3 A
|
| Rated operational current (Ie) at AC-53 |
75 A
|
| Rated operational current (Ie) at AC-53, in-delta |
112.5 A
|
| Rated operational current for specified heat dissipation (In) |
75 A
|
| Rated operational power at 220/230 V, 50 Hz |
22 kW
|
| Rated operational power at 400 V, 50 Hz |
37 kW
|
| Rated operational power at 500 V, 50 Hz |
55 kW
|
| Rated operational power in-delta at 220/230 V, 50 Hz |
30 kW
|
| Rated operational power in-delta at 400 V, 50 Hz |
55 kW
|
| Rated operational power in-delta at 500 V, 50 Hz |
75 kW
|
| Rated operational voltage (Ue) - max |
575 V
|
| Ramp/run-up time |
180 s
|
| Shock resistance |
15 g, Mechanical
|
| Suitable for |
Branch circuits, not as BCPD, (UL/cUL)
|
| Tightening torque |
0.5 Nm, Screw terminals, Control circuit cables
4 Nm, Main cables |
| Short-circuit protection rating |
100NHG00B or NZMH2-A160-BT, Type "1" coordination, Main conducting paths
170M3013 "Type 2" coordination, Main conducting paths |
| Start voltage |
Max. 600% FLA, Min. 100% FLA, Soft start function
|
| Startup class |
CLASS 20 (heavy starting duty 3 x Iₑ for 45 s)
CLASS 10 (star-delta replacement) CLASS 30 (6 x Iₑ for 30 s) |
| Terminal capacity (flexible with ferrule) |
1 x (6 - 70) mm², Main cables
1x (1 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid) |
1 x (6 - 70) mm², Main cables
1x (1 - 2.5) mm², Control circuit cables |
| Terminal capacity (solid/stranded AWG) |
1 x (10 - 2/0), Main cables
1x (28 - 12) , Control circuit cables |