| Product Name |
Eaton Tripp Lite series SmartPro UPS
|
| Catalog Number |
SMART3000RMXL2U
|
| UPC |
037332144324
|
| Product Length/Depth |
23.7 in
|
| Product Height |
3.4 in
|
| Product Width |
17.2 in
|
| Product Weight |
74.5 lb
|
| Compliances |
FCC Class A
RoHS |
| Certifications |
CSA certified
NOM UL 1778 |
| Topology |
Line-interactive
|
| Rack size |
2U
|
| Color |
Black
|
| VA rating |
3000 VA
|
| Wattage |
3000 W
|
| Rack mounting kit |
Yes
|
| Package contents |
|
| Input connection |
L5-30P
|
| Input cord length |
10 ft
|
| Nominal frequency |
50/60 Hz
|
| Input frequency range |
50/60 Hz
|
| Input power factor |
1
|
| Receptacle |
|
| Number of Outputs 5-20R |
6
|
| Number of Outputs L5-30R |
1
|
| Output waveform |
Sine wave
|
| Output nominal voltage |
120V default (100/110/120/125V)
|
| Electric current - max |
24A
|
| Runtime graph |
|
| Battery replacement |
Pre-July 2023: RBC58-2U
Post-July 2023: 744-A3122
|
| Battery type |
Valve Regulated Lead Acid (VRLA)
|
| Extended battery capability |
Extended runtime supported via BP72VRM2U optional external battery packs
|
| Runtime at half load |
9 min
|
| Expansion slots |
|
| User interface |
LCD display
|
| Noise level |
50 dBA maximum, front side 1m
|
| Relative humidity |
20-95% non-condensing
|
| Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
|
| Input Plug Type |
NEMA L5-30P
|
| Output Receptacles |
L5-30R
5-20R |
| Product Features |
Individually Controllable Load Banks
Expandable Runtime Emergency Power Off (EPO)/Remote On-Off (ROO) |
| Product Highlights |
Protects equipment against blackouts, brownouts, transient surges and line noise
ENERGY STAR 2.0-certified to save electricity, lower costs and protect the environment For remote monitor and control, the WEBCARDLXE is required (sold separately). Not compatible with WEBCARDLX. Keeps equipment running during outages to allow time for file saves and safe shutdown $250,000 Ultimate Lifetime Insurance (U.S., Canada and Puerto Rico only) 2 year warranty, 3 year with registration. (Worldwide) Note: Registration is required for 3 year warranty. Unity power factor ensures maximum power possible at each power rating 2-line front-panel LCD with 10 selectable screens reports detailed UPS and site power info |
| PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Office software at https://tripplite.eaton.com/poweralert
|
| Nominal Output Voltage |
100V
110V 120V 125V |
| Network Management Cards |
WEBCARDLXE
|
| Network Management Cards Details |
One slot for optional WEBCARDLXE web card. Note: Not compatible with WEBCARDLX
|
| Output power factor |
1
|
| Phase (input) |
Single-phase
|
| Runtime at full load |
3 min. (3000W)
|
| Communication interface |
Slot for SNMP / Web interface
Contact closure DB9 Serial USB (HID enabled) USB and DB9 serial cables included |
| Battery Access |
Front panel battery access door
|
| Typical Battery Runtime |
Expandable Runtime
|
| Expandable Runtime Description |
Pre-July 2023: BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)
Post-July 2023: BP72VRM2U (limit 4)
|
| Dc Voltage |
72
|
| Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
| Communications Cable |
USB and DB9 cabling included
|
| Grounding Details |
Rear panel grounding lug
|
| Optional Mounting Accessory Notes |
Optional 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm)
|
| Output Circuit Breakers |
Three 20A output breakers protect 2x 5-20R outlets each
|
| Load Management Receptacles |
Two switchable single outlet 5-20R load banks
|
| High Voltage Transfer to Battery Power |
151
|
| Low Voltage Transfer to Battery Power |
80
|
| Undervoltage Correction |
Boost incoming voltages between 81-102V by 15% (Normal Mode); 71-92V by 15% (Extended Mode)
|
| Network UPS Tools (NUT) Compatibility |
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite
|
| Application |
|
| Switch configuration |
5 pushbutton switches control OFF / ON power status, ENTER, UP, and DOWN selection and ESC control functions
|
| AC suppression joule rating |
380
|
| Housing material |
Steel
|
| Output AC waveform (AC mode) |
Pure Sine wave
|
| Output AC waveform (battery mode) |
Pure Sine wave
|
| Output Capacity (kVA) |
3
|
| Output Capacity (Watts) |
3000
|
| Operating Elevation |
|
| Primary UPS Depth (mm) |
602
|
| Primary UPS Height (mm) |
86
|
| Primary UPS Width (mm) |
437
|
| AC Suppression Response Time |
Instantaneous
|
| Alarm Interface |
Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing
|
| Audible Alarms |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
|
| Battery Start Capability |
Cold-start operation supported
|
| Cooling Method |
Fan
|
| Battery Replacement Description |
Hot-swappable, replaceable batteries
|
| Minimum Required Rack Depth With External Battery Pack |
27
|
| Minimum Required Rack Depth Without External Battery Pack |
27
|
| Output Voltage Regulation (Line Mode) |
120V (-13%, +15%)
|
| Output Voltage Regulation(Battery Mode) |
-10%, +6%
|
| Overvoltage Correction |
Reduces incoming voltage between 132-151V by 13% (Normal Mode); 138-152V (Extended mode)
|
| Rechargeable Battery |
Less than 5 hours from 10 to 90% (typical, full load discharge)
|
| Recommended Electrical Service |
30A 120V
|
| Storage Temperature |
5° to 122°F (-15° to 50°C)
|
| Form factor |
Rackmount
Wall-mount Tower |
| Included Mounting Accessory Description |
Included mounting bracket enables installation in 4 post racks. Two ABS mounting stands enables the UPS to be configured in an upright tower orientation.
|
| Input Nominal Voltage Description |
80V-151V; adjustable to 70-153V
|
| Network Monitoring Port Description |
Network Card Optional. Not compatible with WEBCARDLX.
|
| Nominal Voltage Details |
120v nominal output in battery mode
|
| Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 81 to 150V (Normal mode) adjustable to 70-153V (Extended mode)
|
| Maximum Input Amps |
24
|
| Minimum Required Rack Depth (cm) |
68.58
|
| Minimum Required Rack Depth (inches) |
27
|
| UPS Input Cord Length (m) |
3.1
|
| UPS Power Module Dimensions |
3.4 x 17.2 x 23.7
|
| Power Mode Transfer Time |
1-4ms for normal mode, >5ms for sensitive mode
|
| Connected Equipment Insurance |
$250,000 Ultimate Lifetime Insurance |
| Optional Accessories |
4 post rackmount short-depth (4POSTRAILKITWM)
|
| EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
| UPS Input Connection Type |
L5-30P
|
| External Battery Pack Compatibility |
BP72VRM2U (limit 4)
|
| Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS
Individually controllable load banks Schedulable daily hours of economy mode operation |
| Input Nominal Voltage |
120 VAC
|
| High Availability UPS Features |
Expandable battery backup
Hot swappable batteries Automatic voltage regulation (AVR) Remote management Sine wave output Surge/noise protection |
| Nominal Input Voltage Supported |
120 VAC
|