Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 1400A 1000V
Product Name |
Eaton Moeller series NZM molded case circuit breaker electronic
|
Catalog Number |
290385
|
Product Length/Depth |
401 mm
|
Product Height |
207 mm
|
Product Width |
210 mm
|
Product Weight |
21 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Amperage Rating |
1400 A
|
Voltage rating |
1000 V - 1000 V
|
Circuit breaker frame type |
NZM4
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Thermal protection
|
Pollution degree |
3
|
Mounting Method |
Built-in device fixed built-in technique
Fixed |
Equipment heat dissipation, current-dependent |
217.56 W
|
Utilization category |
B
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Rated insulation voltage (Ui) |
1000 V
|
Rated operating power at AC-3, 230 V |
450 kW
|
Rated operating power at AC-3, 400 V |
800 kW
|
Switch off technique |
Electronic
|
Degree of protection |
IP20
|
Direction of incoming supply |
As required
|
Electrical connection type of main circuit |
Screw connection
|
Lifespan, mechanical |
10000 operations
|
Overvoltage category |
III
|
Number of poles |
Three-pole
|
Terminal capacity (copper strip) |
Max. 10 segments of 32 mm x 1 mm (2x) at flat conductor terminal
Min. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched) Min. 6 segments of 16 mm x 0.8 mm at flat conductor terminal 10 segments of 50 mm x 1 mm (2x) at 1-hole module plate 10 segments of 80 mm x 1 mm (2x) at rear-side width extension Max. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched) |
Lifespan, electrical |
500 operations at 1000 V AC-1
|
Functions |
Motor protection
Phase failure sensitive |
Type |
Circuit breaker
|
Special features |
|
Rated operational current for specified heat dissipation (In) |
1400 A
|
Rated short-time withstand current (t = 0.3 s) |
19.2 kA
|
Rated short-time withstand current (t = 1 s) |
19.2 kA
|
Short-circuit release non-delayed setting - max |
19600 A
|
Short-circuit release non-delayed setting - min |
1400 A
|
Handle type |
Rocker lever
|
Instantaneous current setting (Ii) - max |
19600 A
|
Instantaneous current setting (Ii) - min |
1400 A
|
Number of operations per hour - max |
60
|
Overload current setting (Ir) - max |
1400 A
|
Overload current setting (Ir) - min |
700 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 1000 V, 50/60 Hz |
15 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
63 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
50 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
50 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz |
37 kA
|
Standard terminals |
Screw terminal
|
Release system |
Electronic release
|
Terminal capacity (aluminum stranded conductor/cable) |
50 mm² - 240 mm² (4x) at 4-hole tunnel terminal
|
Terminal capacity (control cable) |
0.75 mm² - 1.5 mm² (2x)
0.75 mm² - 2.5 mm² (1x) |
Terminal capacity (copper busbar) |
Max. 80 mm x 10 mm (2x) at rear-side width extension
Min. 25 mm x 5 mm at rear-side 1-hole module plate Min. 60 mm x 10 mm at rear-side width extension Max. 50 mm x 10 mm (2x) at rear-side 1-hole module plate Max. 80 mm x 10 mm (2x) direct at switch rear-side connection Max. 50 mm x 10 mm (2x) direct at switch rear-side connection 50 mm x 10 mm (2x) at rear-side 2-hole module plate Min. 25 mm x 5 mm direct at switch rear-side connection M10 at rear-side screw connection |
Terminal capacity (copper solid conductor/cable) |
240 mm² (2x) at rear-side width extension
35 mm² - 185 mm² (4x) at rear-side 2-hole module plate 50 mm² - 240 mm² (4x) at 4-hole tunnel terminal 70 mm² - 240 mm² (6x) at rear-side width extension 185 mm² - 240 mm² (1x) at rear-side 1-hole module plate 50 mm² (4x) at rear-side 2-hole module plate 70 mm² - 185 mm² (2x) at rear-side 1-hole module plate |
Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 400/415 V, 50/60 Hz |
50 kA
|
Rated short-circuit making capacity Icm at 1000 V, 50/60 Hz |
40 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
187 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
187 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
143 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
100 kA
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
275 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|