Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 630A, 1000 V, VE630-S1
| Product Name |
Eaton Moeller series NZM molded case circuit breaker electronic
|
| Catalog Number |
119368
|
| Product Length/Depth |
166 mm
|
| Product Height |
275 mm
|
| Product Width |
140 mm
|
| Product Weight |
6.34 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC
|
| Amperage Rating |
630 A
|
| Voltage rating |
1000 V - 1000 V
|
| Circuit breaker frame type |
NZM3
|
| Features |
Motor drive optional
Protection unit |
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Pollution degree |
3
|
| Mounting Method |
Fixed
Built-in device fixed built-in technique |
| Equipment heat dissipation, current-dependent |
119.07 W
|
| Utilization category |
A
|
| Ambient operating temperature - max |
70 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
40 °C
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Degree of protection |
IP20
|
| Electrical connection type of main circuit |
Screw connection
|
| Lifespan, mechanical |
15000 operations
|
| Overvoltage category |
III
|
| Number of poles |
Three-pole
|
| Terminal capacity (copper strip) |
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)
10 segments of 50 mm x 1 mm (2x) at rear-side width extension Max. 8 segments of 24 mm x 1 mm (2x) at box terminal Max. 10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm at rear-side connection (punched) Max. 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm Min. 6 segments of 16 mm x 0.8 mm at box terminal |
| Lifespan, electrical |
1000 operations at 1000 V AC-1
|
| Functions |
Systems, cable, selectivity and generator protection
|
| Type |
Circuit breaker
|
| Special features |
|
| Position of connection for main current circuit |
Front side
|
| Rated operational current for specified heat dissipation (In) |
630 A
|
| Release system |
Electronic release
|
| Rated short-time withstand current (t = 0.3 s) |
3.3 kA
|
| Rated short-time withstand current (t = 1 s) |
3.3 kA
|
| Short-circuit release delayed setting - max |
4410 A
|
| Short-circuit release delayed setting - min |
472.5 A
|
| Short-circuit release non-delayed setting - max |
5040 A
|
| Short-circuit release non-delayed setting - min |
1260 A
|
| Terminal capacity (control cable) |
0.75 mm² - 2.5 mm² (1x)
0.75 mm² - 1.5 mm² (2x) |
| Terminal capacity (copper busbar) |
Min. 20 mm x 5 mm direct at switch rear-side connection
Max. 30 mm x 10 mm + 30 mm x 5 mm direct at switch rear-side connection M10 at rear-side screw connection Max. 10 mm x 50 mm (2x) at rear-side width extension |
| Terminal capacity (copper solid conductor/cable) |
10 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (2x) at box terminal 16 mm² (1x) direct at switch rear-side connection |
| Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
| Terminal capacity (copper stranded conductor/cable) |
25 mm² - 185 mm² (1x) at tunnel terminal
35 mm² - 240 mm² (1x) at box terminal 25 mm² - 120 mm² (2x) direct at switch rear-side connection 25 mm² - 120 mm² (1x) direct at switch rear-side connection 25 mm² - 120 mm² (2x) at box terminal |
| Terminal capacity (aluminum stranded conductor/cable) |
25 mm² - 185 mm² (1x) at tunnel terminal
50 mm² - 240 mm² (2x) at 2-hole tunnel terminal 50 mm² - 240 mm² (1x) at 2-hole tunnel terminal |
| Handle type |
Rocker lever
|
| Short delay current setting (Isd) - max |
4410 A
|
| Short delay current setting (Isd) - min |
472 A
|
| Instantaneous current setting (Ii) - max |
5040 A
|
| Instantaneous current setting (Ii) - min |
1260 A
|
| Number of operations per hour - max |
60
|
| Overload current setting (Ir) - max |
630 A
|
| Overload current setting (Ir) - min |
315 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 1000 V, 50/60 Hz |
10 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
150 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
130 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
33 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz |
9 kA
|
| Rated short-circuit making capacity Icm at 1000 V, 50/60 Hz |
17 kA
|
| Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
330 kA
|
| Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
286 kA
|
| Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
143 kA
|
| Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
74 kA
|
| Standard terminals |
Screw terminal
|
| Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
330 kA
|
| Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
| Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
| Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 525 V, 50/60 Hz |
65 kA
|
| Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 1000 V AC |
15 kA
|
| Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
| Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 690 V, 50/60 Hz |
35 kA
|
| Rated short-circuit breaking capacity Icu (IEC/EN 60947) at 440 V, 50/60 Hz |
130 kA
|
| Rated insulation voltage (Ui) |
1000 V AC
|